| Model |
V-500
|
V-410 |
|
4-10
channels
|
2
channels |
4-10
channels |
2
channels |
| Detection principle |
Catalytic combustion
sensor (Low power) |
Hot wire semiconductor
sensor (Low Power) |
| Detection gases |
combustible gases |
Hydrogen, combustible
gases, crude oil vapor |
| Detection range |
0-100% LEL
|
0-2000 ppm
|
| Indication |
LCD bar graph (with
indication for alarm setting) |
| Alarm setting |
16% LEL standard (Adjustable) |
| Alarm accuracy
|
Less than 25%
of alarm set value |
| Alarm response |
Lee than 30 seconds. |
| Alarm function |
Individual alarm lamp
(red) flashing, self-retained
Master alarm lamp (red) flashing, self-retained
Intermittent buzzer sound, self-retained, sound
level more than 80 dB. |
| Output |
| Individual contact |
: |
1a (100 VAC, 1 A) |
| Group contact |
: |
1c (100 VAC, 1 A) |
| group contact output |
: |
1 (0-6-12 V) |
| Buzzer output |
: |
1 (12 VDC, 10mA) |
|
| Alarm
delay |
10 seconds alarm delay of indication unit is
provided.
|
| Operating Temp. |
0 - 40oC |
| Power
Supply |
100 VAC
10%, 50/60 HZ (200 VAC set available) |
| Power
consumption |
Diffusion
type: (16 + 2.5 x n) VA, Suction type: (16 + 7
x n) VA |
Backup
power supply
(4 channels or more) |
Battery: Sealed lead
battery, (12V, 2.2 AH x 2) |
|
Available time of backup (20oC)
| No.
of detector head |
Diffusion type |
Suction type |
| 4 |
120 min.
or more |
60 min.
or more |
| 6 |
90 min. or more |
50 min. or more |
| 8 |
70 min. or more |
40 min. or more |
| 10 |
60 min. or more |
30 min. or more |
|
| Mounting method |
Wall mount |
| Weight |
4-channel type
|
2-channel type
|
4-channel type
|
2-channel type
|
|
approx. 7.5 kg,
incl backup battery
|
approx. 2.5 kg.
|
approx. 7.5 kg,
incl backup battery
|
approx. 2.5 kg.
|
| Coating
color |
Munsell
N8.0 |
| External
Alarm |
(Option)
EB-5 intrinsic safety grade 2G4 with Zener barrier |
| Maintenance
mode |
Indicator:
Peak hold, Buzzer: Stops in 5 seconds after detecting
gas, Relay: Operation stop |